Af-600 fp high power operating instructions – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 152

Advertising
background image

Analog inputs:

Number of analog inputs

2

Terminal number

53, 54

Modes

Voltage or current

Mode select

Switch S201 and switch S202

Voltage mode

Switch S201/switch S202 = OFF (U)

Voltage level

: 0 to + 10 V (scaleable)

Input resistance, R

i

approx. 10 kΩ

Max. voltage

± 20 V

Current mode

Switch S201/switch S202 = ON (I)

Current level

0/4 to 20 mA (scaleable)

Input resistance, R

i

approx. 200 Ω

Max. current

30 mA

Resolution for analog inputs

10 bit (+ sign)

Accuracy of analog inputs

Max. error 0.5% of full scale

Bandwidth

: 200 Hz

The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

Pulse inputs:

Programmable pulse inputs

2

Terminal number pulse

29, 33

Max. frequency at terminal, 29, 33

110 kHz (Push-pull driven)

Max. frequency at terminal, 29, 33

5 kHz (open collector)

Min. frequency at terminal 29, 33

4 Hz

Voltage level

see section on Digital input

Maximum voltage on input

28 V DC

Input resistance, R

i

approx. 4 kΩ

Pulse input accuracy (0.1 - 1 kHz)

Max. error: 0.1% of full scale

Analog output:

Number of programmable analog outputs

1

Terminal number

42

Current range at analog output

0/4 - 20 mA

Max. resistor load to common at analog output

500 Ω

Accuracy on analog output

Max. error: 0.8 % of full scale

Resolution on analog output

8 bit

The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

Control card, RS-485 serial communication:

Terminal number

68 (P,TX+, RX+), 69 (N,TX-, RX-)

Terminal number 61

Common for terminals 68 and 69

The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the supply voltage (PELV).

AF-600 FP High Power Operating Instructions

150

8