Af-600 fp high power operating instructions – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual
Page 159
Mains Supply 3 x 525- 600 VAC
P250
P315
P355
Typical Shaft output at 550 V [kW]
250
315
355
Typical Shaft output at 575 V [HP]
350
400
450
Unit
Size
IP21
42
42
51
Unit Size IP54
42
42
51
Unit
Size
IP00
44
44
52
Output current
Continuous
(at 550 V) [A]
360
418
470
Intermittent (60 sec overload)
(at 550 V) [A]
396
460
517
Continuous
(at 575 V) [A]
344
400
450
Intermittent (60 sec overload)
(at 575 V) [A]
378
440
495
Continuous KVA
(at 550 V) [KVA]
343
398
448
Continuous KVA
(at 575 V) [KVA]
343
398
448
Max. input current
Continuous
(at 550 V ) [A]
355
408
453
Continuous
(at 575 V) [A]
339
390
434
Max. cable size, mains, motor and
load share [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
4 x 240
(4 x 500 mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses [A]
1
500
550
700
Estimated power loss
at rated max. load [W]
4)
5821
6149
6449
Weight,
Unit Size IP21, IP 54 [kg]
151
165
263
Weight,
Unit Size IP00 [kg]
138
151
221
Efficiency
4)
0.98
Output
frequency
0 - 600 Hz
0 - 500 Hz
0 - 500 Hz
Heatsink overtemp. trip
110 °C
110 °C
85 °C
Power card ambient trip
60 °C
60 °C
68 °C