Af-600 fp high power operating instructions – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 159

Advertising
background image

Mains Supply 3 x 525- 600 VAC

P250

P315

P355

Typical Shaft output at 550 V [kW]

250

315

355

Typical Shaft output at 575 V [HP]

350

400

450

Unit

Size

IP21

42

42

51

Unit Size IP54

42

42

51

Unit

Size

IP00

44

44

52

Output current
Continuous
(at 550 V) [A]

360

418

470

Intermittent (60 sec overload)
(at 550 V) [A]

396

460

517

Continuous
(at 575 V) [A]

344

400

450

Intermittent (60 sec overload)
(at 575 V) [A]

378

440

495

Continuous KVA
(at 550 V) [KVA]

343

398

448

Continuous KVA
(at 575 V) [KVA]

343

398

448

Max. input current

Continuous
(at 550 V ) [A]

355

408

453

Continuous
(at 575 V) [A]

339

390

434

Max. cable size, mains, motor and
load share [mm

2

(AWG)]

2 x 185

(2 x 350 mcm)

2 x 185

(2 x 350 mcm)

4 x 240

(4 x 500 mcm)

Max. cable size, brake [mm

2

(AWG)]

2 x 185

(2 x 350 mcm)

2 x 185

(2 x 350 mcm)

2 x 185

(2 x 350 mcm)

Max. external pre-fuses [A]

1

500

550

700

Estimated power loss
at rated max. load [W]

4)

5821

6149

6449

Weight,
Unit Size IP21, IP 54 [kg]

151

165

263

Weight,
Unit Size IP00 [kg]

138

151

221

Efficiency

4)

0.98

Output

frequency

0 - 600 Hz

0 - 500 Hz

0 - 500 Hz

Heatsink overtemp. trip

110 °C

110 °C

85 °C

Power card ambient trip

60 °C

60 °C

68 °C

AF-600 FP High Power Operating Instructions

157

8

Advertising