Digital output:

Programmable digital/pulse outputs

2

Terminal number

27, 29

1)

Voltage level at digital/frequency output

0 - 24 V

Max. output current (sink or source)

40 mA

Max. load at frequency output

1 kΩ

Max. capacitive load at frequency output

10 nF

Minimum output frequency at frequency output

0 Hz

Maximum output frequency at frequency output

32 kHz

Accuracy of frequency output

Max. error: 0.1 % of full scale

Resolution of frequency outputs

12 bit

1) Terminal 27 and 29 can also be programmed as input.

The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

Control card, 24 V DC output:

Terminal number

12, 13

Max. load

: 200 mA

The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs and outputs.

Relay outputs:

Programmable relay outputs

2

Relay 01 Terminal number

1-3 (break), 1-2 (make)

Max. terminal load (AC-1)

1)

on 1-3 (NC), 1-2 (NO) (Resistive load)

240 V AC, 2 A

Max. terminal load (AC-15)

1)

(Inductive load @ cosφ 0.4)

240 V AC, 0.2 A

Max. terminal load (DC-1)

1)

on 1-2 (NO), 1-3 (NC) (Resistive load)

60 V DC, 1A

Max. terminal load (DC-13)

1)

(Inductive load)

24 V DC, 0.1A

Relay 02 Terminal number

4-6 (break), 4-5 (make)

Max. terminal load (AC-1)

1)

on 4-5 (NO) (Resistive load)

2)3)

400 V AC, 2 A

Max. terminal load (AC-15)

1)

on 4-5 (NO) (Inductive load @ cosφ 0.4)

240 V AC, 0.2 A

Max. terminal load (DC-1)

1)

on 4-5 (NO) (Resistive load)

80 V DC, 2 A

Max. terminal load (DC-13)

1)

on 4-5 (NO) (Inductive load)

24 V DC, 0.1A

Max. terminal load (AC-1)

1)

on 4-6 (NC) (Resistive load)

240 V AC, 2 A

Max. terminal load (AC-15)

1)

on 4-6 (NC) (Inductive load @ cosφ 0.4)

240 V AC, 0.2A

Max. terminal load (DC-1)

1)

on 4-6 (NC) (Resistive load)

50 V DC, 2 A

Max. terminal load (DC-13)

1)

on 4-6 (NC) (Inductive load)

24 V DC, 0.1 A

Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)

24 V DC 10 mA, 24 V AC 20 mA

Environment according to EN 60664-1

overvoltage category III/pollution degree 2

1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300 V AC 2A

Control card, 10 V DC output:

Terminal number

50

Output voltage

10.5 V ±0.5 V

Max. load

25 mA

The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

Control characteristics:

Resolution of output frequency at 0 - 1000 Hz

: +/- 0.003 Hz

System response time (terminals 18, 19, 27, 29, 32, 33)

:

≤ 2 ms

Speed control range (open loop)

1:100 of synchronous speed

Speed accuracy (open loop)

30 - 4000 rpm: Maximum error of ±8 rpm

All control characteristics are based on a 4-pole asynchronous motor

AF-600 FP High Power Operating Instructions

151