AP-23 No-Flow Function

Option:

Function:

Common actions for Low Power Detection and Low Speed Detection (Individual selections not possible).

[0] *

Off

[1]

Sleep Mode

[2]

Warning

Messages in the keypad display (if mounted) and/or signal via a relay or a digital output.

[3]

Alarm

The frequency converter trips and motor stays stopped until reset.

AP-24 No-Flow Delay

Range:

Function:

10 s*

[1 - 600 s]

Set the time Low Power/Low Speed must stay detected to activate signal for actions. If detection disap-
pears before run out of the timer, the timer will be reset.

AP-26 Dry Pump Function

Option:

Function:

Low Power Detection must be Enabled (par. AP-21 Low Power Detection) and commissioned (using either
par. AP-3#, No Flow Power Tuning, or par. AP-20 Low Power Auto Set-up) in order to use Dry Pump De-
tection.

[0] *

Off

[1]

Warning

Messages in the keypad display (if mounted) and/or signal via a relay or a digital output.

[2]

Alarm

The frequency converter trips and motor stays stopped until reset.

AP-40 Minimum Run Time

Range:

Function:

10 s*

[0 - 600 s]

Set the desired minimum running time for the motor after a start command (digital input or Bus) before
entering Sleep Mode.

AP-41 Minimum Sleep Time

Range:

Function:

10 s*

[0 - 600 s]

Set the desired Minimum Time for staying in Sleep Mode. This will override any wake up conditions.

AP-42 Wake-up Speed [RPM]

Range:

Function:

0 RPM*

[par. F-18 - par. F-17 RPM]

To be used if par. K-02 Motor Speed Unit has been set for RPM (parameter not visible if Hz selected). Only
to be used if par. H-40 Configuration Mode is set for Open Loop and speed reference is applied by an
external controller.
Set the reference speed at which the Sleep Mode should be cancelled.

AP-60 Broken Belt Function

Option:

Function:

Selects the action to be performed if the Broken Belt condition is detected

[0] *

Off

[1]

Warning

[2]

Trip

AP-61 Broken Belt Torque

Range:

Function:

10 %*

[0 - 100 %]

Sets the broken belt torque as a percentage of the rated motor torque.