EXAMPLE 2:
Variable= FEEDBACK, range= -200% to +200%
Range needed for output= 0-100%
Output signal 0 or 4 mA is needed at 0% (50% of range) - set par. AN-51 Terminal 42 Output Min Scale to 50%
Output signal 20 mA is needed at 100% (75% of range) - set par. AN-52 Terminal 42 Output Max Scale to 75%

130BA856.10

EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%), 0-10 mA
Output signal 0 or 4 mA is needed at Min ref - set par. AN-51 Terminal 42 Output Min Scale to 0%
Output signal 10 mA is needed at Max ref (100% of range) - set par. AN-52 Terminal 42 Output Max Scale to 200%
(20 mA / 10 mA x 100%=200%).

130BA857.10

AP-21 Low Power Detection

Option:

Function:

[0] *

Disabled

[1]

Enabled

If selecting Enabled, the Low Power Detection commissioning must be carried out in order to set the
parameters in group AP-3# for proper operation!

AP-22 Low Speed Detection

Option:

Function:

[0] *

Disabled

[1]

Enabled

Select Enabled for detecting when the motor operates with a speed as set in par. F-18 Motor Speed Low
Limit [RPM]
or par. F-16 Motor Speed Low Limit [Hz].

AF-600 FP High Power Operating Instructions

95