Af-600 fp high power operating instructions, 12 fuses, 13 fuse tables – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 25

Advertising
background image

3.1.12 Fuses

Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and
over-current protected according to national/international regulations.

Short-circuit protection:
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. GE recommends using the fuses mentioned below to protect
service personnel and equipment in case of an internal failure in the drive. The frequency converter provides full short-circuit protection in case of a short-circuit
on the motor output.

Over-current protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. Fuses or circuit breakers can be used to provide the over-
current protection in the installation. Over-current protection must always be carried out according to national regulations.

3.1.13 Fuse tables

380-480 V, frame sizes 4X, 5X and 6X
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 480V/600V depending on the drive voltage rating. With the
proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.

AF-600

FP

Bussmann

E1958

JFHR2**

Bussmann

E4273

T/JDDZ**

SIBA

E180276

RKI/JDDZ

LittelFuse

E71611

JFHR2**

Ferraz-

Shawmut

E60314

JFHR2**

Bussmann

E4274

H/JDDZ**

Bussmann

E125085

JFHR2*

Internal

Option

Bussmann

150 HP

FWH-

300

JJS-

300

2028220-

315

L50S-300

A50-P300

NOS-

300

170M3017

170M3018

200 HP

FWH-

350

JJS-

350

206xx32-

315

L50S-350

A50-P350

NOS-

350

170M3018

170M3018

250 HP

FWH-

400

JJS-

400

206xx32-

400

L50S-400

A50-P400

NOS-

400

170M4012

170M4016

300 HP

FWH-

500

JJS-

500

206xx32-

500

L50S-500

A50-P500

NOS-

500

170M4014

170M4016

350 HP

FWH-

600

JJS-

600

206xx32-

600

L50S-600

A50-P600

NOS-

600

170M4016

170M4016

Table 3.3: For Unit Sizes 41, 42, 43, and 44,380-480 V

AF-600 FP

Bussmann PN*

Rating

Ferraz

Siba

450 HP

170M4017

700 A, 700 V

6.9URD31D08A0700

20 610 32.700

500 HP

170M6013

900 A, 700 V

6.9URD33D08A0900

20 630 32.900

550 HP

170M6013

900 A, 700 V

6.9URD33D08A0900

20 630 32.900

600 HP

170M6013

900 A, 700 V

6.9URD33D08A0900

20 630 32.900

Table 3.4: For Unit Sizes 51 and 52, 380-480 V

AF-600 FP

Bussmann PN*

Rating

Siba

Internal Bussmann Option

650 HP

170M7081

1600 A, 700 V

20 695 32.1600

170M7082

750 HP

170M7081

1600 A, 700 V

20 695 32.1600

170M7082

900 HP

170M7082

2000 A, 700 V

20 695 32.2000

170M7082

1000 HP

170M7082

2000 A, 700 V

20 695 32.2000

170M7082

1200 HP

170M7083

2500 A, 700 V

20 695 32.2500

170M7083

1350 HP

170M7083

2500 A, 700 V

20 695 32.2500

170M7083

Table 3.5: Unit Sizes 61, 62, 63, and 64, 380-480 V

AF-600 FP

Bussmann PN*

Rating

Siba

650 HP

170M8611

1100 A, 1000 V

20 781 32.1000

750 HP

170M8611

1100 A, 1000 V

20 781 32.1000

900 HP

170M6467

1400 A, 700 V

20 681 32.1400

1000 HP

170M6467

1400 A, 700 V

20 681 32.1400

1200 HP

170M8611

1100 A, 1000 V

20 781 32.1000

1350 HP

170M6467

1400 A, 700 V

20 681 32.1400

Table 3.6: Unit Sizes 61, 62, 63, and 64, Inverter module DC Link Fuses, 380-480 V

*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be
substituted for external use
**Any minimum 480 V UL listed fuse with associated current rating may be used to meet UL requirements.

AF-600 FP High Power Operating Instructions

24

3

Advertising