The L_LCB_LogicControlBasic library

L_LCB_ActuatorSpeed

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Outputs

xDriveSetQSP

BOOL

TRUE: Activate quick stop

xResetError

BOOL

TRUE: Reset error message (acknowledged)

xEnableSpeedSetpoint

BOOL

TRUE: Speed control activated

• The inputs xJogSet1, xJogSet2 and rSpeedSetPoint are evaluated.

xJog1Set

BOOL

TRUE: Jog 1 activated

• Speed setpoint 1 requested

• Active if xEnableSpeedSetpoint = TRUE

xJog2Set

BOOL

TRUE: Jog 2 activated

• Speed setpoint 2 requested

• Active if xEnableSpeedSetpoint = TRUE

xInvertDirectionSet

BOOL

TRUE: Inversion of the direction of rotation of the motor (clockwise rotation/

counter-clockwise rotation)

rSpeedSetpoint

REAL

Setpoint selection for the speed in [%]

• Active if...

xEnableSpeedSetpoint = TRUE and xJog1Set = FALSE and xJog2Set = FALSE

Identifier/data type

Information/possible settings

xError

BOOL

"Error" status signal

FALSE Conversion carried out without errors

TRUE Error during the conversion

eError

L_LCB_Error

Error number, error code

xCommunicationOk

BOOL

Status of bus communication

FALSE No bus communication active

TRUE Bus communication available

xInternalControlActive

BOOL

TRUE: The output signals that the xEnableInternalControl input and the Internal

Control button of the visualisation have been activated.

• The control via visualisation is activated.

xDriveError

BOOL

Status signal "Error in controller"

xDriveWarning

BOOL

TRUE: Controller is in "Warning" device state

xDriveReady

BOOL

Status signal "Controller is ready for operation"

xDriveEnabled

BOOL

TRUE: Controller has been enabled

xDriveQSPActive

BOOL

TRUE: Quick stop active

xSpeedEqZero

BOOL

TRUE: Speed is zero

xDirectionCCW

BOOL

Display of the direction of rotation of the motor

TRUE:CCW rotation is active

xHW_Input1

BOOL

Digital input 1 is active

xHW_Input2

BOOL

Digital input 2 is active

Identifier/data type

Information/possible settings