1 setting up communication to the controller, Commissioning – Lenze PLC Designer R3-x User Manual

Page 19

Advertising
background image

Lenze · Commissioning of Lenze drives · 1.3 EN - 06/2014

19

Commissioning

Wiring the hardware

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.2.1

Setting up communication to the Controller

• Connect the Engineering PC with the controller via a network cable, as the »PLC Designer«

accesses the controller via Ethernet.

• Make the IP settings with the »PLC Designer«.

How to check the communication settings:

1. Go to the Device view and double-click the desired L-force Controller.
2. Make the desired settings on the Communication settings tab.

• Click the Add gateway button to insert a gateway.
• Enter the desired IP address of the L-force Controller.

[5-2]

Example: Entering the IP address of the L-force Controller

3. Click OK to add the controller as gateway.
4. By double-clicking the desired channel (or clicking the Set active path button) set the

channel selected in the device tree below the gateway as active path for control.

• Thus, all communication actions directly refer to this channel.
• The currently active path is represented in bold in the list and "(active)" is attached:

5. A device represented in italics is set as momentarily active path but has not been found by

the last network scan.

Note!

• During initial commissioning, observe the following predefined IP addresses:

• Engineering PC: 192.168.5.100
• Controller: 192.168.5.99