Extending sample projects - adding devices

Setting of CAN parameters and PDO mapping

60

Lenze · Commissioning of Lenze drives · 1.3 EN - 06/2014

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

2. Go to the PDO Mapping tab.

By default, the PDO mapping is optimised for the corresponding application. It is possible

to change this mapping (set checkmark). Due to the limited bandwidth of the CAN bus, this

is only sensible in special cases. The PDO properties are pre-assigned sensibly as well and

should not be changed.
By double-clicking a single PDO, you can see its transmission properties.

• The

Transmission Type "cyclic - synchronous (type 1-240)" and

the setting, at

which sync the PDOs are to be sent, must not be changed.

• The settings for the

Inhibit Time and the

Event Time are not evaluated.

• Confirm the settings with OK.

On the CANopen I/O Mapping tab, PLC variables can be assigned to the process image.

Note!

Bus operation without CAN synchronisation

• The control system always transmits asynchronous PDOs from an unsolicited task in

an event-controlled way. To achieve a time-controlled transmission of asynchronous

PDOs by the control system, you must assign the CAN master to a cyclic task.

• The control does not support any monitoring times for asynchronous receive-PDOs.

This is only possible with field devices.