Frequency set group (cont.) – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual

Page 100

Advertising
background image

Chapter 5 – Programming

5-28

Frequency Set Group (cont.)

[Skip Freq Band]

Parameter # 35

Factory Default 0 Hz

[Skip Freq Band]

Parameter Type Read & Write

Minimum 0 Hz

This parameter determines the band width around a [Skip
Frequency]
. The band width is 2

 [Skip Freq Band]

1/2 the band above and 1/2 the band below the [Skip
Frequency]
setting. “0” Disables All Skip Frequencies.

Units 1 Hz

Maximum 15 Hz

'

Figure 5.15 Skip Frequency Band

b

y

Two times

[Skip Freq Band]

Setting

'

Command Frequency

Skip Frequency

Frequency

Time

Drive Output
Frequency

Setting

a

[MOP Increment]

Parameter # 22

Factory Default 0.00 Hz/Sec

[MOP Increment]

Parameter Type Read & Write

Minimum 0.00

y

The MOP function is a digital solid-state circuit that
produces the same effect as rotating a speed reference
potentiometer with a small DC motor. This permits local
(HIM) or remote (TB2) control of the command
frequency. This parameter sets the rate of increase or
decrease to the [MOP Hertz] command frequency for
each input to the MOP Increment or MOP Decrement
terminals of TB2. (Requires the proper [Input Mode]
selection or serial communications.)

Units 1 Hz/Sec

Maximum 255 Hz/Sec

'

y

Hz
(Speed)

INC

Time

DEC