Output configuration group (cont.) – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual

Page 110

Advertising
background image

Chapter 5 – Programming

5-38

Output Configuration Group (cont.)

[Analog Out Sel]

Parameter # 25

Factory Default “Frequency”

[Analog Out Sel]

Parameter Type Read & Write

This parameter selects the value to which the 0-10V DC

u pu

T

s pr p r

Units None

Setting ‘‘Frequency”

0 to [Maximum Freq]

This parameter selects the value to which the 0-10V DC
analog output at TB2-5 is proportional to.

‘‘Current”

0 to 200% of Rated Drive Output Current)

u pu

T

s pr p r

‘‘Bus Volts”

0 to Maximum Bus Voltage– 410V/230V Drives

815V/460V Drives

‘‘Power”

0 to 200% of Drive Rated OutputPower

“Output Volts”

0 to Drive Rated Voltage

[Above Freq Val]

Parameter # 77

Factory Default 0 Hz

[Above Freq Val]

Parameter Type Read & Write

Minimum 0 Hz

This parameter sets the level at which Output 1 or Output 2
will transition when [Output 1 Config] or [Output 2
Config]
are set to ‘‘Above Freq”. This provides an
indication that the drive is operating above the
programmed frequency value.

Units Hertz

Maximum 400 Hz

NOTE: This parameter can not be programmed
while the drive is running.

[Above Curr Val]

Parameter # 142

Factory Default 0 % of Drive Rated Current ➀

[Above Curr Val]

Parameter Type Read & Write

Minimum 0 % of Drive Rated Current ➀

This parameter sets the level at which Output 1 or Output 2
will transition when [Output 1 Config] or [Output 2
Config]
are set to ‘‘Above Curr”. This provides an
indication that the drive output current exceeds the
programmed value.

Units 1%

Maximum 150% of Drive Rated Current ➀

The drive rated output current is based on three phase input ratings. See page 5-14 for Single Phase Input Rating instructions.