Chapter 5 – Programming

5-39

Faults

This group of parameters provides information and programmed settings on commonly viewed drive faults.

[Fault Buffer 0-3]

Parameter # 86-89

Factory Default None

[Fault Buffer 0-3]

Parameter Type Read Only

These parameters store the last (4) faults that occur. If the
same fault occurs multiple times in a row, it will only be
stored once. [Fault Buffer 0] through [Fault Buffer 3] can
only be cleared by ‘‘Reset Defaults” from EEPROM mode
or [Set Defaults] parameter. This will leave a ‘‘F48” in
[Fault Buffer 0] and reset all parameters to factory
defaults.

Units None

Buffer

0
1

2
3

Last Fault, stored in EEPROM
Fault from Buffer 0, Stored in EEPROM
Fault from Buffer 1, Stored in EEPROM
Fault from Buffer 2, Stored in EEPROM

[Clear Fault]

Parameter # 51

Factory Default ‘‘Ready”

[Clear Fault]

Parameter Type Read & Write

This parameter is used to clear a fault and return the drive
to ready status if the fault condition no longer exists.
IMPO TA T:

lear a l

s p ru

dr ve

s

Units None

Displays ‘‘Ready”

Display after function has been attempted

IMPORTANT: [Clear Fault] will stop a running drive. Also
[Clear Fault] does not clear [Fault Buffer 0] through
[Fault Buffer 3].

‘‘Clear Fault”

Attempts to clear fault

IMPORTANT:To clear a fault using parameter #51, press the SEL key once to select the bottom display line. Press the ▲ ▼ keys
until “Clear Fault” appears on the bottom display line. Press the

key. This action will attempt to clear the fault. “Ready” will be

displayed. Press the ESC key several times to get back to the Status Display and check if the fault has been cleared. If the fault has
not been cleared refer to the Troubleshooting section of this manual.