Chapter 2 – Installation/Wiring

2-16

Table 2.E Maximum Motor Cable Length

Drive HP

(4

)

Motor HP

(4

)

Reactor

at the Drive

With 1204-TFB2 Terminator

With 1204-TFA1 Terminator

r e HP

(460V)

Mo or HP

(460V)

Using a Motor with Insulation V

P-P

Using a Motor with Insulation V

P-P

Using a Motor with Insulation V

P-P

1000 Volt

1200 Volt or 1600 Volt

M

P-P

1000 Volt or 1200 Volt

1000 Volt

1200 Volt

Any Cable

Shielded

Unshielded

Shielded

Unshielded

Shielded

Unshielded

Shielded

Unshielded

Maximum Carrier Frequency

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

High-Line Derating Multiplier

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

5

5

15m (50ft)

182m (600ft)

182m (600ft)

NR

NR

91m (300ft)

61m (200ft)

91m (300ft)

121m (400ft)

3

15m (50ft)

182m (600ft)

182m (600ft)

91m (300ft)

121m (400ft)

99m (325ft)

61m (200ft)

152m (500ft)

121m (400ft)

2

15m (50ft)

182m (600ft)

182m (600ft)

121m (400ft)

182m (600ft)

99m (325ft)

61m (200ft)

182m (600ft)

121m (400ft)

1

15m (50ft)

182m (600ft)

182m (600ft)

121m (400ft)

182m (600ft)

99m (325ft)

61m (200ft)

182m (600ft)

121m (400ft)

0.5

15m (50ft)

182m (600ft)

182m (600ft)

182m (600ft)

182m (600ft)

99m (325ft)

61m (200ft)

182m (600ft)

121m (400ft)

3

3

15m (50ft)

91m (300ft)

182m (600ft)

NR

NR

91m (300ft)

61m (200ft)

91m (300ft)

121m (400ft)

2

15m (50ft)

182m (600ft)

182m (600ft)

91m (300ft)

121m (400ft)

99m (325ft)

61m (200ft)

152m (500ft)

121m (400ft)

1

15m (50ft)

182m (600ft)

182m (600ft)

91m (300ft)

182m (600ft)

99m (325ft)

61m (200ft)

182m (600ft)

121m (400ft)

0.5

15m (50ft)

182m (600ft)

182m (600ft)

121m (400ft)

182m (600ft)

99m (325ft)

61m (200ft)

182m (600ft)

121m (400ft)

2

2

15m (50ft)

76m (250ft)

167m (550ft)

NR

NR

91m (300ft)

61m (200ft)

91m (300ft)

121m (400ft)

1

15m (50ft)

182m (600ft)

182m (600ft)

61m (200ft)

61m (200ft)

99m (325ft)

61m (200ft)

121m (400ft)

121m (400ft)

0.5

15m (50ft)

182m (600ft)

182m (600ft)

91m (300ft)

121m (400ft)

99m (325ft)

61m (200ft)

152m (500ft)

121m (400ft)

1

1

15m (50ft)

68m (225ft)

152m (500ft)

NR

NR

45m (150ft)

61m (200ft)

45m (150ft)

76m (250ft)

0.5

15m (50ft)

121m (400ft)

182m (600ft)

NR

NR

76m (250ft)

61m (200ft)

76m (250ft)

121m (400ft)

0.5

0.5

15m (50ft)

45m (150ft)

106m (350ft)

NR

NR

NR

NR

NR

NR

NR = Not Recommended.

IMPORTANT: A 3% reactor reduces motor stress but may cause a degradation of motor waveform quality. Reactors must have a turn-to-turn insulating rating of 2100 volts or
higher. Reactors are not recommended for lightly loaded applications because overvoltage trips may result at low output frequencies.