Appendix b – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual

Page 155

Advertising
background image

Appendix B –

Serial Communications

B-7

Table B.4 Parameter Grouping/User Settings (cont.)

Group

Parameter Name

Parameter #

Display

Units

Drive Units

Scale Factor

Min

Max

Factory Setting

User‘s

Setting

Minimum Freq

16

Hz

1

0

120

0

Maximum Freq

19

Hz

1

40

400

60

Base Frequency

17

Hz

1

40

400

60

Base Voltage

18

Volts

1

25% of
DRV

Maximum Drive Rated Volts

Maximum DRV

Break Frequency

49

Hz

1

0

120

4 Hz

Up

Break Voltage

50

Volts

1

0

50% of Max Drive Rated Volts

Drive Size
Dependent

ed Set U

Maximum Voltage

20

Volts

1

25% of
DRV

Maximum Drive Rated Volts

Maximum DRV

n

ce

d

DC Boost Select

9

Text ➀

1

––

––

Break Point

A

dva

n

Start Boost

48

Volts

1

0

25% of Max. Drive Rated Volts

Drive Size
Dependent

A

Run Boost

83

Volts

1

0

25% of Max. Drive Rated Volt

0

PWM Frequency

45

kHz

10

2.0

8.0

4.0

Analog Invert

84

Text ➀

1

––

––

Disabled

4–20 mA Loss Sel

81

Text ➀

1

––

––

Stop/Fault

Stop Select

10

Text ➀

1

––

––

Ramp

DC Hold Time

12

Seconds

1

0

15

0

DC HoId Level

13

Volts

1

0

25% of Max. Drive Rated Volt

0

DB Enable

11

Text ➀

1

––

––

Disabled

Motor Type

41

Text ➀

1

––

––

Induc/Reluc

Compensation

52

Text ➀

1

––

––

No Comp

Refer to Table B.5 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions. Refer to page B-2.

Advertising