Chapter 6 – Troubleshooting and Fault Information

6-10

Table 6.C Troubleshooting (cont.)

General Problem

Action to Take

Motor not accelerating properly.

(1) Check motor

- Verify that motor is connected properly.
- Verify that no mechanical problems exist.

2) Check control input signals

- Verify that SW1, SW2, and SW3 are in the proper state to select desired Accel/Decel rates.

(Refer to Table 5.A on page 5-29)

(4) Check parameter settings and charts on Pages 5-29 and 5-30.

- Verify that [Accel Time 1] and [Accel Time 2] are set properly.
- Verify that [Current Limit] is set properly.
- Verify that [DC Boost Select] is set correctly.
- Verify that [Start Boost] and [Run Boost] are set properly.

Specific Problem

Action to Take

Can not Jog from Adapter.

(1) Verify that [Jog Mask] is set properly to allow jogging from that adapter.
(2) Verify that [Logic Mask] is set properly to allow jogging from that adapter.
(3) Is drive already running?
(4) Examine [Stop Owner] to verify that a maintained Stop does not exist.

Can not change direction from Adapter.

(1) Verify that [Direction Mask] is set to allow direction changes from that adapter.
(2) Verify that [Logic Mask] is set to allow direction changes from that adapter.

Can not Start from Adapter.

(1) Verify that [Start Mask] is set properly to allow starting from that adapter.
(2) Verify that [Logic Mask] is set properly to allow starting from that adapter.
(3) Is drive already running?
(4) Examine [Stop Owner] to verify that a maintained Stop does not exist.

Display indicates “Not Enabled”.

(1) Check enable signal at TB2, terminals 11 & 12.