Chapter 5 – Programming

5-18

Advanced Set Up Group (cont.)

[DC Boost Select]

Parameter # 9

Factory Default ‘‘Break Point”

[DC Boost Select]

Parameter Type Read & Write

This parameter sets the level of DC boost at low
frequencies. It also selects special Volts-per-Hz patterns.

Units None

Settings ‘‘No Boost”

‘‘6 Volts”
‘‘12 Volts”
‘‘18 Volts’’
‘‘24 Volts’’
‘‘30 Volts’’
‘‘36 Volts’’
‘‘42 Volts’’
‘‘48 Volts’’
‘‘Break Point’’
‘‘Run Boost’’
‘‘Fan Sel #1’’
‘‘Fan Sel #2”

See Figure 5.8
See Figure 5.8
See Figure 5.8
See Figure 5.8
See Figure 5.8
See Figure 5.8
See Figure 5.8
See Figure 5.8
See Figure 5.8
See Figure 5.7
See Figure 5.10
See Figure 5.9
See Figure 5.9

[Base Voltage]
[Base Frequency]

Figure 5.8 Standard Boost Volts-per-Hz Pattern

Motor Rated

'

a [Maximum Voltage]
[Maximum Frequency]

b

y

Motor Rated

0 –

0

Voltage

Frequency

Active when [DC Boost Select] is
set to ‘‘No Boost” or ‘‘6 Volts”
through ‘‘48 Volts.”

No Boost

48

6

[Base Voltage]
[Base Frequency]

b

0

0

Voltage

1/2 Base Frequency

b

35% Base Voltage

Fan Sel #2

' a Fan Select #1

45% Base Voltage

Figure 5.9 Fan/Pump Volts-per-Hz Pattern

These patterns are active only
when [DC Boost Select] is set
to ‘‘Fan Sel #1” or ‘‘Fan Sel #2.”

a [Maximum Voltage]
[Maximum Frequency]