Chapter 5 – Programming

5-13

Set Up Group (cont.)

[Sec Curr Limit]

Parameter # 141

Factory Default 0% of Drive Rated Current ➁

[Sec Curr Limit]

Parameter Type Read & Write

Minimum 0% of Drive Rated Current ➁

When this parameter is set to zero, the [Current Limit]
setting is used throughout the frequency range. When set
to a value other than zero, the [Current Limit] value will
be active up to the [Base Frequency] setting, then tapers
down between [Base Frequency] and 1.5 times [Base
Frequency]
. At frequencies above 1.5 times [Base
Frequency]
, the [Sec Curr Limit] setting is the active
current limit value.

Units 1%

Maximum 150% of Drive Rated Current ➁

Figure 5.5 Current Limit Setting

% of Drive Output Current

[Base Frequency]

(17)

1.5 Times

[Base Frequency]

[Maximum Frequency]

(19)

a [Current Limit]

(36)

a [Sec Curr Limit]

(141)

(17)