Power wiring – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual

Page 27

Advertising
background image

Chapter 2 – Installation/Wiring

2-11

POWER WIRING

Input and output power connections are performed through a
ten position terminal block, TB1 (see page 2-3 for location).

Figure 2.6 Power Terminal Block Designations (TB1)

GRD

GRD

L1

R

L2

S

L3

T

+DC BRK➀

(-DC)

T1

U

T2

V

T3

W

Required Branch

Circuit Disconnect

AC Input Line

To Motor

Connection for Dynamic Brake Resistors for all models except the 200-230 Volt,

0.37 to 0.75 kW (1/2 to 1 HP) drive. IMPORTANT: The [DB Enable] parameter must
be enabled for proper operation.

For single phase applications, the AC input line can be connected to any two of

the three input terminals R, S, T (L1, L2, L3).

Bulletin 1305 drives are UL and cUL listed, and CSA certified as a motor overload

protective device. An external overload relay is not required for single motor applica-
tions. IMPORTANT: This drive is not intended for use with single phase motors.

Ground from drive to motor frame must be an independent continuous insulated

wire run.

To

Motor

Required

Input Fusing

Table 2.B Power Block Terminal (TB1)

Terminals

Description

GRD

Earth Ground

R, S, T (L1, L2, L3)

AC Input Line Terminals

+DC, BRK (or -DC)

Dynamic Brake Option - Refer to instructions included
with option

U, V, W (T1, T2, T3)

Motor Connection

Table 2.C Screw Size, Wire Size and Torque Specifications

Terminal

Screw
Size

Max./Min. Wire Size
mm

2

(AWG

)

Maximum Torque
N-m ( lb-ins. )

TB1
(0.37 to 0.75kW/1/2 to 1 HP)

M4

3.5/0.75 (12/18)

0.90 (8)

TB1 (All except above)

M4

4/0.75 (10/18)

1.81 (16)

TB2 (All)

M3.5

1.5/0.20 (14/24)

0.90 (8)

Advertising