Chapter 5 – Programming

5-56

This group contains parameters that can be used to display a drive parameter in ‘‘User Units.”

Process Display

[Process Par]

Parameter # 127

Factory Default 1

[Process Par]

Parameter Type Read & Write

Minimum 1

This parameter should be set to the number of the
parameter whose scaled value will be displayed on
Line 1 of the HIM Display Panel when in process mode.

Units Numeric

Maximum Max. Parameter Number

[Process Scale]

Parameter # 128

Factory Default +1.00

[Process Scale]

Parameter Type Read & Write

Minimum –327.68

This value sets the scaling multiplier for [Process Par].
The displayed value will be:

[Process Par] actual value

[Process Scale] value

Displayed Value ➀

Units Numeric

Maximum +327.67

[Process Txt 1-8]

Parameter #(s) 129-136

Factory Default ‘‘?’’

[Process Txt 1-8]

Parameter Type Read & Write

These parameters set the ‘‘User Units” description for
the value determined by [Process Par] and [Process
Scale].
This text is displayed on Line 1 of the HIM.

Units ASCII Text

Character

The maximum value that can be displayed is 99,999.99. If this value is exceeded a
character string of asterisks (

*******

) will appear on the display.