Adapter i/o – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual

Page 126

Advertising
background image

Chapter 5 – Programming

5-54

Adapter I/O

This group contains the parameters needed for an optional communications adapter to communicate with the drive.

[Data In A1 through D2]

Parameter # 111 - 118

[Data In A1 through D2]

Parameter Type Read & Write

These parameters are used to write real time data values
from a source controller (PLC, SLC, etc.) to the drive. This
is accomplished by programming a parameter number into
the [Data In] parameters. The value programmed into the
source controller’s output image table will be written to the
drive parameter identified in the corresponding [Data In]
parameter.

IMPORTANT

IMPORTANT:

The drive parameter that is

accessed indirectly using Data In will not be
stored permanently and automatically to
EEPROM (due to the high potential update rate
from a PLC). A manual operation is necessary
for permanent storage. The HIM EEPROM
command, Save Values, or using parameter (64)
[Set Defaults] will perform this task. Similarly,
to restore the values to the ones the drive had
before Data In was configured, the HIM Recall
Values Function can be used.

IMPORTANT:

[Preset Freq 1] through

[Preset Freq 7] are not accessible with these
parameters in firmware version FRN 4.01 and
earlier.

Data In A1
Data In A2
Data In B1
Data In B2
Data In C1
Data In C2
Data In D1
Data In D2

Bulletin 1305 drive

Controller Output Image Table (i.e. PLC, SLC, etc.)

IMPORTANT: addressing information that defines which controller
I/O address corresponds to a [Data In] parameter is determined by
the dip switch settings on the external communication module.
Refer to the appropriate Bulletin 1203 Communication Module User
Manual for details.

Refer to Appendix B for additional information.

111
112
113
114
115
116
117
118

Parameter

Advertising