Chapter 5 – Programming

5-34

Feature Select Group (cont.)

[S Curve Time]

Parameter # 56

Factory Default 0.0 Sec

[S Curve Time]

Parameter Type Read & Write

Minimum 0.0 Sec

This parameter enables an adjustable shape S-Curve
accel/decel time. IMPORTANT: [S-Curve Time] must be
set to a value less than or equal to the Accel & Decel
times.

Units 0.1 Second

Maximum 300.0 Sec

a 1/2 '

S-Curve

Time

a 1/2 '

S-Curve

Time

a Decel Time '

1 or 2

a Accel Time '

1 or 2

Figure 5.17 S-Curve Time

Enabled

Disabled

a1/2 '

S-Curve

Time

[S-Curve Enable] must be ‘‘enabled” for this
parameter to be active. The [S-Curve Time]
setting is added to the active accel/decel times
to form an adjustable S-Curve.

IMPORTANT: If [Stop Select] is set to “S
Curve” then the decel time will be double the
active decel setting when a stop command is
provided.

a1/2 '

S-Curve

Time

[Language]

Parameter # 47

Factory Default Alternate language in multilingual versions,

English in English only versions.

Parameter Type Read & Write

This parameter selects between English and the alternate
second language that can be displayed on the HIM.

Units None

Settings ‘‘English” or

“French”
“Italian”
“Spanish”
“German”

Advertising