Faults group (cont.) – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual

Page 112

Advertising
background image

Chapter 5 – Programming

5-40

Faults Group (cont.)

[Cur Lim Trip En]

Parameter # 82

Factory Default ‘‘Default Run”

[Cur Lim Trip En]

Parameter Type Read & Write

This setting determines whether or not exceeding the
se

rren L

use

s

urre

Units None

Setting ‘‘Trip @ I Lim”

A Diagnostic Current Limit Fault is generated

setting in [Current Limit] will cause a Diagnostic Current
Limit Fault (Fault F36).

‘‘Default Run”

No fault generated

[Line Loss Fault]

Parameter # 40

Factory Default ‘‘F03 Enable”

[Line Loss Fault]

Parameter Type Read & Write

This setting determines whether a 15% drop in DC Bus
voltage will have no effect on operation or cause a ‘‘Power

ss

u

u

)

Units None

Setting ‘‘UVolt Run”

‘‘Power Loss Fault” Disabled

Loss Fault” (fault F03).

IMPORTANT

:

The “Line Loss” alarm bit will be set when

this condition exists regardless of the parameter setting.

‘‘FO3 Enable”

Drive Trips at 85% of nominal bus voltage.