Advanced setup – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual

Page 87

Advertising
background image

Chapter 5 – Programming

5-15

This group contains parameters that are required to setup advanced functions of the drive such as custom
Volts per Hertz settings and dynamic braking.

Advanced Setup

[Minimum Freq]

Parameter # 16

Factory Default 0 Hz

[Minimum Freq]

Parameter Type Read & Write

Minimum 0 Hz

This parameter sets the lowest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq].

Units 1 Hz

Maximum 120 Hz

IMPORTANT: This parameter can not be
programmed while the drive is running.

[Maximum Freq]

Parameter # 19

Factory Default 60 Hz

[Maximum Freq]

Parameter Type Read & Write

Minimum 40 Hz

This parameter sets the highest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq]

Units 1 Hz

Maximum 400 Hz

IMPORTANT: This parameter can not be
programmed while the drive is running.

[Base Frequency]

Parameter # 17

Factory Default 60 Hz

[Base Frequency]

Parameter Type Read & Write

Minimum 40 Hz

This value should be set to the motor nameplate Rated
Frequency.

Units 1 Hz

Maximum 400 Hz

Units 1 Hz

Maximum 400 Hz

Advertising