Chapter 5 – Programming

5-19

Advanced Set Up Group (cont.)

[Start Boost]

Parameter # 48

Factory Default See Table

[Start Boost]

Parameter Type Read & Write

Minimum 0 Volts

1/2
HP

3/4
HP

1

HP

2

HP

3

HP

5

HP

230V

20

Volts

25

Volts

20

Volts

22

Volts

19

Volts

N/A

This parameter sets the DC boost level for acceleration
when [DC Boost Select] is set to ‘‘Run Boost” or ‘‘Break
Point.”

Units 1 Volt

Maximum 25% of

Max. Drive
Rated
Volts

460V

31

Volts

45

Volts

40

Volts

37

Volts

33

Volts

26

Volts

Figure 5.10 Start/Run Boost

[Base Voltage]
[Base Frequency]

b

0 –

0

Voltage

Frequency

[Start Boost]

'

[Run Boost]

'

Active when [DC
Boost Select] is
set to
‘‘Run Boost”

a 150% of Start Boost

a 150% of Run Boost

[Run Boost]

Parameter # 83

Factory Default 0 Volts

[Run Boost]

Parameter Type Read & Write

Minimum 0 Volts

This parameter sets the DC boost level for constant speed
level when [DC Boost Select] is set to ‘‘Run Boost.” [Run
Boost]
must be set at a value less than [Start Boost].

Units 1 Volt

Maximum 25% of Max. Drive Rated Volts