Chapter 5 – Programming
5-20
Advanced Set Up Group (cont.)
[PWM Frequency]
Parameter # 45
Factory Default 4.0 kHz
[PWM Frequency]
Parameter Type Read & Write
Minimum 2.0 kHz
This parameter sets the carrier frequency for the PWM
output waveform. IMPORTANT: Output Current derating
applies above 4kHz. See Fig. 5-11.
Units 0.1 kHz
Maximum 8.0 kHz
Figure 5.11 PWM Frequency Derating
1
2
3
4
5
6
7
8
84
86
88
90
92
94
96
98
100
% Output Current (A)
Carrier Frequency, kHz
IMPORTANT: Ignoring derating guidelines can
cause reduced drive performance.
IMPORTANT:Changing PWM carrier frequency may result in changes in Start-up and Holding current if start boost and DC
Holding voltages are in effect. These parameters should be checked if the carrier frequency is changed and reprogrammed if
needed.