Chapter 6 – Troubleshooting and Fault Information

6-8

Table 6.B Bulletin 1305 Fault Descriptions (cont.)

Fault Name & Number

Fault Description

Action to Take

Undervolt Fault

DC Bus voltage fell below the minimum value. [Line Loss

a l p r

e er s pr r

ed

u

Monitor the incoming AC line for low voltage or line power

errup

Undervolt Fault
F4

DC Bus voltage fell below the minimum value. [Line Loss
Fault]
parameter is programmed to “U Volt Run”.

Monitor the incoming AC line for low voltage or line power
interruption.

UV Short Fault
F41

Excessive current has been detected between these two drive
output terminals.

Check the motor and external wiring to the drive output terminals
for a shorted condition.

UW Short Fault
F42

Excessive current has been detected between these two drive
output terminals.

Check the motor and external wiring to the drive output terminals
for a shorted condition.

VW Short Fault
F43

Excessive current has been detected between these two drive
output terminals.

Check the motor and external wiring to the drive output terminals
for a shorted condition.