Faults group (cont.) – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual

Page 113

Advertising
background image

Chapter 5 – Programming

5-41

Faults Group (cont.)

Line Loss Fault “U Volt Run” (Disabled)

Line Loss Fault “F03 Enable” (Enabled)

No Fault

No Fault

No Fault

Power Loss Fault

Undervolt
Fault

100% Nominal
Bus Voltage

85% Nominal
Bus Voltage

Minimum Bus
Voltage

100% Nominal
Bus Voltage

85% Nominal
Bus Voltage

Minimum Bus
Voltage

Undervolt
Fault

➀ Minimum bus voltage is approximately 70% of Line Voltage

Output Power is on

Output Power is on

No Output Power

No Output

Power

Output Power is on

T

1

T

2

T

3

T

4

T

5

T

6

Application Notes: If line loss is set to ‘‘U Volt Run” and [Run On Power Up] is enabled, the drive will run as long as the bus
voltage is high enough to maintain logic.

To obtain longer power ride-thru, choose “U Volt Run”. This allows the output power to be on from time T

1

to T

3

. To obtain a

longer control ride–thru, choose “F03 Enable”. The output power devices are turned off at time T

5

but note that time T

6

– T

5

is

greater than time T

3

– T

2

.

[Flt Clear Mode]

Parameter # 39

Factory Default ‘‘Enabled”

[Flt Clear Mode]

Parameter Type Read & Write

This parameter controls the method for clearing faults.

Units None

Setting ‘‘Enabled”

Faults Cleared By Issuing a Valid Stop Command or
Cycling Input Power

‘‘Disabled”

Faults Cleared Only By Cycling Input Power

Advertising