Chapter 5 – Programming
5-14
Single Phase Input Ratings
The [Current Limit], [Overload Current] and [Sec Curr
Limit] parameters are set based on the drive rated output
current for three phase input ratings. When setting these
parameters for single phase input ratings, use the following
formula to determine the proper parameter setting:
1
O Output Current➂ X Percent (0 to 150%)
3
O Output Current ➂
Parameter setting
in percent
=
➁
The Drive Rated Ouput Current is based on three phase input ratings. See Single
Phase Input Ratings instructions.
➂
See Table 1.A on page 1-6.