Chapter 3 – Human Interface Module

3-12

EEPROM MODE

ACTION

DESCRIPTION

HIM DISPLAY

or

or

ESC

Reset Defaults

❏ 1. The EEPROM mode is used to restore all settings to factory default values

or to upload or download parameters between the HIM and the drive.
(Parameter upload or download requires a Series B HIM).

To restore factory defaults:

a. From the Status Display, press Enter (or any key). “Choose Mode” will

be displayed.

b. Press the Increment (or Decrement) key until “EEPROM” is displayed.

If EEPROM is not in the menu, programming is password protected.
Refer to Password Mode later in this section.

c. Press Enter.

d. Press the Increment (or Decrement) key until “Reset Defaults” is

displayed.

e. Press Enter to restore all parameters to their original factory settings.

f. Press ESC. “Reprogram Fault” will display.

g. Press the Stop key to reset the fault.

IMPORTANT: If [Input Mode] was previously set to a value other
than “1,” cycle drive power to reset.

Choose Mode
Display

Choose Mode
EEProm

Reprogram Fault
F 48

Stopped

+0.00 Hz

EEProm
Reset Defaults