Chapter 5 – Programming

5-33

Feature Select Group (cont.)

[Reset/Run Time]

Parameter # 15

Factory Default 1.0 Sec

[Reset/Run Time]

Parameter Type Read & Write

Minimum 0.5 Sec

This value sets the time between restart attempts when
[Reset/Run Tries] is a value other than zero.
IMPORTANT: [Reset/Run Tries] is a cumulative count.
This counter resets to zero if four (4) minutes elapses
since the last fault.

Units 0.1 Second

Maximum 30.0 Sec

[S Curve Enable]

Parameter # 57

Factory Default ‘‘Disabled”

[S Curve Enable]

Parameter Type Read & Write

This parameter enables a fixed shape S-Curve.

Units None

Settings ‘‘Enabled”

‘‘Disabled”

a

Accel Time

'

1 or 2

aDecel Time '

1 or 2

Enabled

Disabled

a 2X Accel Time 1 or 2 '

a 2X Decel Time 1 or 2 '

Figure 5.16 S-Curve

Accel/Decel times are double the active accel/decel time
settings.
IMPORTANT: The setting for [S-Curve Time] must be 0.

IMPORTANT: If [Stop Select] is set to “S Curve”
then the decel time will be double the active decel
setting when a stop command is provided.