Doors.NET Reference Manual

- 377 -

10. Highlight the reader for Door 2 and again locate the Anti-Passback settings.

l

Anti-Passback Mode - must be set to Hard

l

Enter Area - must be set to Door 2 (or the name assigned to the second area)

l

Exit Area must be set to Door 1 (or the name assigned to the first area)

11. The Airlock setup/configuration is then complete, so the next step is to present a

valid card at Door 1, then open the door contact when access is granted.

12. With the door contact still open for Door 1, present the same card to Door 2 - You

will get Access Denied and in Live Events the full message will be:

13. You will only be able to get access at Door 2 again when the Door 1 door contacts

are in the closed state.

14. And you will only be able to get access through Door 1 when the contacts for Door

2 are closed.