Doors.NET Reference Manual

- 399 -

l

No Floor Select means all outputs will activate for all floors to which a cardholder
has access when they present and authenticate their credential to the elevator cab
reader. So if a cardholder has total access, all twenty outputs will change state,
which in effect will allow any of the floor selection buttons to be pressed in the cab
in order to access any of the floors.

l

With Floor Select does not activate any of the outputs until an input is pressed fol-
lowing a valid card read. Once input 1 has been pressed, output 1 will fire; input 2
will fire output 2, etc. This information is then stored in the system database so that
at a later time reports can be run to see which floors cardholders have accessed.

18. The controller now shows the reader on bus 1 is designated as the elevator reader,

the other readers on the controller are removed from the hardware tree. The output
relays for each of the buses are changed from Strike Outputs to Elevator Outputs
and all are associated with the elevator reader.

19. Reset the controller, restart the MSC gateway, and perform a controller update to

ensure the new elevator control configuration information has been uploaded to
the controller.

20. Verify the reader and the outputs are correctly linked. Right-click the elevator cab

reader on bus 1, select temp unlock, and then click the Unlock button while ‘All
Floors’ is highlighted.