Firmware updates for hardware components, Rim v03.01.11, Known issues – Keri Systems Doors.NET Manual User Manual

Page 56: Doors.net version 3.5.1.9, New features / improvements, Program corrections, Doors.n7, V3.5.1.9

Advertising
background image

Doors.NET Reference Manual

- 56 -

Firmware Updates for Hardware Components:

RIM v03.01.11

l

Under certain conditions, typically when “hot-swapping” readers or in unusually
EMI noisy environments, the RIM’s Data0 and Data1 lines could be pulled into a
both-lines-low state. This is illegal per the Wiegand specification, and because of
this it was not properly managed by the firmware. Changes were made in the firm-
ware to recognize this state and prevent this condition from being processed.

Known Issues:

l

There is a communication time out issue in that a communication attempt can
timeout before it is completed on a slow network such as a wireless network or
VPN, or if a very large number of credentials are sent to a controller.

Doors.NET Version 3.5.1.9

New Features / Improvements:

l

The Admin Client now has a video camera configuration option.

l

An Applet Tray feature has been added allowing for direct and easy management
of the Doors.NET services used by the program.

l

A basic, context sensitive version of Online Help has been added.

l

Revision-to-revision software upgrades are now fully handled by the installer.

Program Corrections:

l

The Default Administrator could change its account type which meant the Default
Administrator could change its own permissions and no longer be able to control
other operator or application permissions. This is no longer allowed for the Default
Administrator.

l

When updating controller status, the Gateway was not returning a time stamp for
the returned controller status.

l

When a controller with peripheral hardware was removed from a system, the con-
troller was correctly removed from the database, but the inputs and outputs for the
controller's peripherals were still listed in the database. Peripheral hardware is
now correctly removed.

l

When setting an alert to require a password on confirmation, the Confirm button
was not enabled after entering the password.

l

The GIOX Firmware Upgrade revision list did not differentiate between GIOX firm-
ware and any other firmware revision. It now lists only GIOX firmware revisions.

l

If an alert was marked as In Progress the next alert to follow would not give the
alert sound, but all subsequent alerts would.

Advertising