3-8

Electrical Installation

Installation with Only a Neutral Conductor Provided

Installations where no grounding conductor is provided must comply with article 250-32 of
the National Electrical Code. If the installation in question meets all of the requirements of
article 250-32, the following guidelines must be observed:

• Connect the grounding electrode cable at the local disconnect, never at the display power

termination panel.

• A disconnect that opens all of the ungrounded phase conductors should be used.
• The neutral and the ground conductors should be bonded in the display power termination

panel.


Refer to Figure 37 for installation details.

3.6

Bringing Signal to the Display

Reference Drawings:

V1500 Signal Termination..................................................................... Drawing A-103727

Serial Line IF Signal Terms................................................................... Drawing A-103740

Figure 36: Installation with Ground and Neutral Conductor Provided

Figure 37: Installation with only Neutral Conductor provided