5.7 H: Terminal Functions

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

207

P

a

ra

me

te

r De

ta

ils

5

Setting 61: Motor pole search status

This terminal changes states when the Initial Motor Pole Position Search is finished.

Refer to n8-35: Initial Rotor

Position Detection Selection on page 236

for details on Motor Pole Position Search.

Use this setting in applications where the motor speed feedback is supplied from a non-absolute encoder (e.g.,
incremental) and where the drive brake sequence is not utilized.

Design the external brake sequence to interlock the brake as long as the Motor Pole Position Search has not finished. In
this case, the external brake sequence should be designed to interlock the brake during Motor Pole Position Search.

Setting 100 to 161: Functions 0 to 61 with Inverse Output

These settings have the same function as settings 0 to 61 but with inverse output. Set as 1††, where the “1” indicates
inverse output and the last two digits specify the setting number of the function.

Examples:

• For inverse output of “8: During baseblock”, set 108.

H3: Multi-Function Analog Inputs

The drive is equipped with two multi-function analog input terminals: A1 and A2. Refer to

Table 5.13

for a listing of the

functions that can be set to these terminals.

H3-01: Terminal A1 Signal Level Selection

Selects the input signal level for analog input A1.

Setting 0: 0 to 10 Vdc

The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and
bias settings will be read as 0%.

Setting 1: –10 to 10 Vdc

The input level is –10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then the
motor will rotate in reverse.

H3-02: Terminal A1 Function Selection

Selects the input signal level for analog input A1. Refer to

Multi-Function Analog Input Terminal Settings on page 209

for instructions on how to adjust the signal level.

<1> The search process takes 0.5 to 5.0 s depending on the Motor Pole Position Search method selected in n8-35 and whether Motor Pole

Search Error detection is enabled in parameter n8-86.

No.

Parameter Name

Setting Range

Default

H3-01

Terminal A1 Signal Level Selection

0 or 1

0

No.

Parameter Name

Setting Range

Default

H3-02

Terminal A1 Function Selection

0 to 1F

0

Up/Down command

Motor pole search status

Brake interlock

Brake can be released

Motor pole position
search process

<1>

common_TM