Writing to Multiple Registers

Function code 10H allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This process
works similar to reading registers, in that the address of the first register to be written and the data quantity are set in the
command message. The data to be written must be consecutive so that the register addresses are in order, starting from the
specified address in the command message. The data order must be high byte then lower byte.

The following table shows an example of a message where a forward (Up) operation has been set with a speed reference
of 100.00% for the slave 1 drive.

If parameter values are changed using the Write command, an Enter command may be necessary to activate or save the
data depending on the setting of H5-11.

Refer to H5-11: Communications Enter Function Selection on page 424

and

Refer to Enter Command on page 442

for detailed descriptions.

Note: Double the number of the data quantity for the number of bytes in the command message.

Torque Compensation Through MEMOBUS/Modbus Communications

Perform the steps below to utilize Torque Compensation Through MEMOBUS/Modbus Communications.

Torque Compensation Set-up via MEMOBUS/Modbus

1.

Set H3-01, H3-02: to 14 Torque Compensation.

2.

Set MEMOBUS/Modbus Register 0F, bit 3 = Enable Torque Compensation.

3.

MEMOBUS/Modbus Register 0005H = Torque Compensation, signed
a. Setting value Pre-Run, w/Run, or Post-Run per application needs.

Troubleshooting Torque Compensation Set-up via MEMOBUS/Modbus

1.

If an error message occurs when sending the Torque Compensation value.
a. Set H5-07 (RTS): 1 0.

2.

Modbus Register 0F, bit 3 = Enable Torque Limit and Torque Comp (H3-02 = 1F).
a. Runaway condition

3.

Modbus Register 0005H should be signed (-3000 to +3000)
a. Register has internal limit from 0 to positive values.
i. Negative values are set to "0".

Command Message

Response Message (normal)

Response Message (fault)

Slave Address

01H

Slave Address

01H

Slave Address

01H

Function Code

10H

Function Code

10H

Function Code

90H

Starting No.

Upper

00H

Starting No.

Upper

00H

Error Code

02H

Lower

01H

Lower

01H

CRC-16

Upper

CDH

Data Quantity

Upper

00H

Data Quantity

Upper

00H

Lower

C1H

Lower

02H

Lower

02H

Number of Bytes

04H

CRC-16

Upper

10H

Starting Data

Upper

00H

Lower

08H

Lower

01H

Next Data

Upper

27H

Lower

10H

CRC-16

Upper

79H

Lower

9FH