B.3 Parameter Table

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

371

Pa

ra

met

er

L

is

t

B

C2: Jerk Settings

C3: Slip Compensation

C1-06

(205H)

Deceleration Ramp 3 (Motor 2
Decel Time 1)

Sets the ramp to decelerate from maximum speed to 0.

Default: 1.50 s

<6> <8>

Min: 0.00 s
Max: 600.00 s

<6> <8>

162

C1-07

(206H)

Acceleration Ramp 4 (Motor 2
Accel Time 2)

Sets the ramp to accelerate from 0 to maximum speed.

C1-08

(207H)

Deceleration Ramp 4 (Motor 2
Decel Time 2)

Sets the ramp to decelerate from maximum speed to 0.

C1-09

(208H)

Fast Stop Ramp

Sets the ramp for the Fast Stop function.

163

C1-10

(209H)

Accel/Decel Setting Resolution

0: 0.01 s unit
1: 0.1 s unit

Default: 0
Min: 0
Max: 1

164

C1-11

(20AH)

Accel/Decel Switching Speed

Sets the speed to switch between accel/decel ramp settings.

Default: 0.0%
Min: 0.0%
Max: 100.0%

163

C1-12

(246H)

Motor 2 Acceleration Time

Sets the acceleration time for motor 2.
Note: Parameter C1-12 determines the acceleration time for motor 2 as long as d1-27 is not set
to 0.00 Hz.

Default: 1.0 s
Min: 0.0 s
Max: 600.0 s

164

C1-13

Motor 2 Acceleration Time

Sets the deceleration time for motor 2.

Default: 1.0 s
Min: 0.0 s
Max: 600.0 s

C1-15

(260H)

Inspection Deceleration Ramp

Sets the deceleration ramp used for inspection run.

Default: 0.00 s

<6> <8>

Min: 0.00 s
Max: 2.00 s

<6> <8>

164

<6> Setting ranges and defaults vary by the setting units determined by parameter o1-03.

Refer to Defaults and Setting Ranges by Display Unit Selection (o1-03) on page 416

.

<8> Setting range value is dependent on parameter C1-10, Accel/Decel Setting Resolution. When C1-10 = 0 (units of 0.01 seconds), the setting

range becomes 0.00 to 600.00 seconds.

No.(Addr.)

Name

Description

Setting

Page

C2-01

(20BH)

<6> Setting ranges and defaults vary by the setting units determined by parameter o1-03.

Refer to Defaults and Setting Ranges by Display Unit Selection (o1-03) on page 416

Jerk at Accel Start

Five different jerk values can be set. They are automatically applied as shown in the figure
below.

Default: 0.50 s

<6>

Min: 0.00 s
Max: 10.00 s

<6>

164

C2-02

(20CH)

Jerk at Accel End

Default: 0.50 s

<6>

Min: 0.00 s
Max: 10.00 s

<6>

C2-03

(20DH)

Jerk at Decel Start

Default: 0.50 s

<6>

Min: 0.00 s
Max: 10.00 s

<6>

C2-04

(20EH)

Jerk at Decel End

Default: 0.50 s

<6>

Min: 0.00 s
Max: 10.00 s

<6>

C2-05

(25FH)

Jerk below Leveling Speed

Sets the jerk used when the speed reference is lower than the leveling speed setting

Default: 0.50 s

<6>

Min: 0.00 s
Max: 10.00 s

<6>

No.(Addr.)

Name

Description

Setting

Page

C3-01

(20FH)

Slip Compensation Gain

Sets the gain for the motor slip compensation function.

Default: 1.0

Min: 0.0
Max: 2.5

165

C3-02

(210H)

Slip Compensation Primary Delay
Time

Adjusts the slip compensation function delay time.

Default: 2000 ms

Min: 0 ms
Max: 10000 ms

165

No. (Addr.)

Name

Description

Setting

Page

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

CLV

CLV/PM

V/f

OLV

common

_

CLV

CLV/PM

V/f

OLV

common

_

All Modes

common

_

All Modes

common

_

Time

C2-01

C2-05

C2-05

C2-04

C2-02

C2-03

ON

Up/Down command

Output speed

OFF

All Modes

common

_

common

_

CLV

CLV/PM

V/f

OLV

common

_

CLV

CLV/PM

V/f

OLV