5.11 S: Elevator Parameters

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

253

P

a

ra

me

te

r De

ta

ils

5

S3-21: Dwell 2 End Speed

The Dwell 2 function will end when the drive reaches this speed. A setting of 0.00 will disable the acceleration rate switch
that occurs at the end of Dwell 2.

S3-25: DC Injection Gain in Regenerative Operation

In OLV Control, S3-25 sets a gain level for DC Injection at stop (S1-03) for when the regenerative load reaches 100%. At
that time, the current applied during DC Injection at stop is determined as S1-03

× S3-25.

S3-26: DC Injection Gain in Motoring Operation

In OLV Control, S3-26 sets a gain level for DC Injection at stop (S1-03) when the motoring load reaches 100%. At that
time, the current applied during DC Injection at stop is determined as S1-03

× S3-26.

S3-27: Torque Compensation Value with Load Condition 1

Adjusts the analog signal from a load sensor for torque compensation.

Refer to Adjusting the Torque Compensation at

Start on page 127

for details.

S3-28: Torque Compensation Value with Load Condition 2

Adjusts the analog signal from a load sensor for torque compensation.

Refer to Adjusting the Torque Compensation at

Start on page 127

for details.

S3-29: Analog Input from Load Sensor with Load Condition 1

Adjusts the analog signal from a load sensor for torque compensation.

Refer to Adjusting the Torque Compensation at

Start on page 127

for details.

S3-30: Analog Input from Load Sensor with Load Condition 2

Adjusts the analog signal from a load sensor for torque compensation.

Refer to Adjusting the Torque Compensation at

Start on page 127

for details.

No.

Parameter Name

Setting Range

Default

S3-21

Dwell 2 End Speed

0.00 to 100.00%

0.00%

No.

Parameter Name

Setting Range

Default

S3-25

DC Injection Gain in Regenerative Operation

0 to 400%

100%

No.

Parameter Name

Setting Range

Default

S3-26

DC Injection Gain in Motoring Operation

0 to 400%

20%

No.

Parameter Name

Setting Range

Default

S3-27

Torque Compensation Value with Load Condition 1

-100.0 to 100.0%

-50.0%

No.

Parameter Name

Setting Range

Default

S3-28

Torque Compensation Value with Load Condition 2

-100.0 to 100.0%

50.0%

No.

Parameter Name

Setting Range

Default

S3-29

Analog Input from Load Sensor with Load Condition 1

-100.0 to 100.0%

0.0%

No.

Parameter Name

Setting Range

Default

S3-30

Analog Input from Load Sensor with Load Condition 2

-100.0 to 100.0%

100.0%