Reference 104S

v2

♦ ProLinx Gateway

Protocol Manual

(Firmware v2.xx)


ProSoft Technology, Inc.

Page 119 of 157

March 19, 2010

Each event contains the following data structure:

Start Byte

End Byte

Data Field(s) Description

0 1

DB

Index

This is the index for the point in the gateway’s
database. This corresponds to the order of point
definition for the gateway data types. This is not the
point address for the event.

2

2

ASDU

This is the ASDU data type for the event message.

1=single point,

3=double-point,

5=step,

9=normalized,

11=scaled,

13=short-float

15=integrated

total.

3 3

Qualifier

This is the qualifier code for the event message. Refer
to the IEC protocol specification for a full listing of valid
qualifier codes for each ASDU type.

4

5

Year

This field contains the four-digit year for the event.

6 6

Month

This field contains the month value for the event. Valid
entry for this field is in the range of 1 to 12.

7 7

Day

This field contains the day value for the event. Valid
entry for this field is in the range of 1 to 31.

8 8

Hour

This field contains the hour value for the event. Valid
entry for this field is in the range of 0 to 23 (bits 0 to 4).
Bit 7 of the byte can be used to set the summer time
flag (0=standard, 1=summer time)

9 9

Minute

This field contains the minute value for the event. Valid
entry for this field is in the range of 0 to 59 (bits 0 to 5).
Bit 7 of the byte can be used to set the invalid bit for
the time (0=valid, 1=invalid).

10 11

Seconds &
Milliseconds

This field contains the seconds and milliseconds value
for the event. Valid entry for this field is in the range of
0 to 59,999.

12 15

Data

These bytes contain the data for the event. For single-
and double-point, step events, the first byte is used.
For measured value events, the first two bytes are
used. For integrated total and short-float events, all four
bytes are used.