IEC-60870-5-104 (104S) Protocol Implementation

104S v2 ♦ ProLinx Gateway

Protocol Manual

(Firmware v2.xx)


ProSoft Technology, Inc.

Page 79 of 157

And assume the Parameter Offets are configured as shown:

M_ME_NA Parameter Offset : 2400 #M_ME_NA IOA offset for parameter data

M_ME_NB Parameter Offset : 2500 #M_ME_NB IOA offset for parameter data

M_ME_NC Parameter Offset : 2600 #M_ME_NC IOA offset for parameter data

It would imply that the parameter points would be configured as follows:

M_ME_NA

Monitored Measured Normalized Point

Associated Parameter Point

400 2400

401 2401

402 2402

403 2403

... ...

409 2409

In order to send a change of deadband for M_ME_NA Point 400, the client would
send a command type 110 to point 2400.