104S v2 ♦ ProLinx Gateway

IEC-60870-5-104 (104S) Protocol Implementation

(Firmware v2.xx)

Protocol Manual


Page 64 of 157

ProSoft Technology, Inc.

3.4.1 Control Data Transfer

The control communication typically occurs when the client sends a command
request to update the gateway’s command points. The data types addressing are
described in the following table.

Data Type

Data Size

Addressing Type

C_SC_NA 1

bit

Bit

C_DC_NA 2

bits

Bit

C_RC_NA 1

byte

Byte

C_SE_NA 1

word

Word

C_SE_NB 1

word

Word

C_SE_NC 2

words

Word

Some of the command points may be configured to be selected before executed.

Refer to the following parameter to configure the select/operate timeout period.
After the gateway receives the SELECT operation it will wait for this period of
time for the EXECUTE operation. If the gateway does not receive an EXECUTE
operation within this period of time it will require another SELECT operation
before the EXECUTE operation.

March 19, 2010