Common Address of ASDU

0 to 65535

This parameter specifies the common address of the ASDU (section address) for
access to data in the gateway. There is only one value entered for access to all
data in the gateway.

Cyclic Data Transmission

0 to 4,294,967,296 (2 raised to the power of 32)

This parameter defines the number of milliseconds between cyclic updates. The
range of values for this parameter permit update times of 1 millisecond to 5
minutes. If the parameter is set to 0, cyclic data reporting will be disabled.

Select/Operate Timeout

0 to 4,294,967,296 (2 raised to the power of 32)

This parameter sets the number of milliseconds after a select command is
received in which to wait for a valid execute command. The range of values for
this parameter permit times of 1 millisecond to 30 seconds. If the parameter is
set to 0, the feature will be disabled.

Use ACTTERM with Setpoint

1 or 0

This parameter determines if an ACTTERM will be sent. If the parameter is set to
1, then setpoint commands will issue an ACTTERM when the command is
complete. If the parameter is set to 0, ACTCON is the last response to a setpoint
command.

Use ACTTERM with Step

1 or 0

This parameter determines if an ACTTERM will be sent. If the parameter is set to
1, then step commands will issue an ACTTERM when the command is complete.
If the parameter is set to 0, ACTCON is the last response to a step command.