IEC-60870-5-104 (104S) Protocol Implementation

104S v2 ♦ ProLinx Gateway

Protocol Manual

(Firmware v2.xx)


ProSoft Technology, Inc.

Page 57 of 157

3.3.2 Monitor Points Addressing

As discussed before, the monitor points must be configured in a database area in
the 104S v2 gateway.

The monitor data types are described in the following table.

Data Type

Data Size

Addressing Type

M_SP_NA 1

bit

Bit

M_DP_NA 2

bits

Bit

M_ST_NA 1

byte

Byte

M_ME_NA 1

word

Word

M_ME_NB 1

word

Word

M_ME_NC 2

word

Double-Word

M_IT_NA 2

word

Double-Word

M_SP_NA

A Monitored Single-Point occupies one binary bit and uses bit-addressing. For
example, if you configured the following points as shown:

The following table describes how these points would be stored in the gateway
memory database.

Inf. Object Address

Gateway Database Address

100

Bit 0 of word 100 (Bit address 1600)

101

Bit 1 of word 100 (Bit address 1601)

102

Bit 2 of word 100 (Bit address 1602)