2.1.2 [IEC-870-5-104]

This section provides information required to configure a server application with
the gateway. Most entries contained within this section are self explanatory.

Use IP List

N

O

(0) or Y

ES

(1)

This parameter specifies if the IP address of the host connected to the system
will be validated. If the parameter is set to N

O

(0), any host may connect to the

unit. If the parameter is set to Y

ES

(1), only hosts in the IP list will be permitted to

connect to the unit.

Override StartDT

N

O

(0) or Y

ES

(1)

This parameter is used when testing the gateway with a simulator or with a Client
unit that does not meet the IEC 60870-5-104 specification. After the Clinet
connects to the gateway, it will send a STARTDT.ACT U-format message to the
gateway to permit the gateway to start sending data. If the Client does not
support this requirement, set the parameter to Y

ES

(1). Set the parameter to N

O

(0) if the Client sends the STARTDT.ACT message.

Note: This parameter must be set to N

O

(0) if you wish to use the redundant Clients feature.