Group codes – ProSoft Technology 5201-DFNT-104S User Manual

Page 36

Advertising
background image

104S v2 ♦ ProLinx Gateway

Configure the Gateway

(Firmware v2.xx)

Protocol Manual


Page 36 of 157

ProSoft Technology, Inc.

March 19, 2010

2.1.18 Group Codes

One aspect of the point configuration database that leads to confusion is the
group definition field. This assignment for each point assigns a point to one or
more interrogation groups. Use of interrogation groups permits the controlling
unit to interface with a specific set of data. Refer to the IEC 60870-5-104
standard for a full discussion of interrogation groups. A specific group, Periodic
data group, reports data points on a set frequency. The frequency is set in the
Cyclic Data Transmission parameter in the configuration file. Remember that a
point can be assigned to more than one group.

Group Code

Description

0x00000001

Interrogated by general interrogation (station or global)

0x00000002

Interrogated by group 1 interrogation

0x00000004

Interrogated by group 2 interrogation

0x00000008

Interrogated by group 3 interrogation (See Note 1, below)

0x00000010

Interrogated by group 4 interrogation

0x00000020

Interrogated by group 5 interrogation

0x00000040

Interrogated by group 6 interrogation

0x00000080

Interrogated by group 7 interrogation

0x00000100

Interrogated by group 8 interrogation

0x00000200

Interrogated by group 9 interrogation

0x00000400

Interrogated by group 10 interrogation

0x00000800

Interrogated by group 11 interrogation

0x00001000

Interrogated by group 12 interrogation

0x00002000

Interrogated by group 13 interrogation

0x00004000

Interrogated by group 14 interrogation

0x00008000

Interrogated by group 15 interrogation

0x00010000

Interrogated by group 16 interrogation

0x00020000

Interrogated by general counter request

0x00040000

Interrogated by group 1 counter request

0x00080000

Interrogated by group 2 counter request

0x00100000

Interrogated by group 3 counter request

0x00200000

Interrogated by group 4 counter request

0x40000000

Disable event scanning of this point

0x80000000

Periodic/cyclic data returned from unit

Note 1: Group 3 interrogation also returns the parameter data (ASDU 110 – threshold, low limit
and high limit) for all monitored measured points.

Advertising