C_SE_NA point count: This parameter specifies the number of point values

assigned for the command normalized-point database. Range is 0 to 1000.

C_SE_NB point count: This parameter specifies the number of point values

assigned for the command scaled-point database. Range is 0 to 1000.

C_SE_NC point count: This parameter specifies the number of point values

assigned for the command short-float point database. Range is 0 to 50.

Sequence Flag

Y

ES

or N

O

In order to save bandwidth, you can configure the gateway to use the Sequence
Flag feature using the following parameters:

If this parameter is set to N

O

, this feature is not selected, the gateway will send

the object address and value for every monitored point sent to the Client, and the
Sequence Flag (SQ) will be set to zero (0).

If this parameter is set to Y

ES

, this feature is selected, the gateway will send the

object point address and value for only the first point of a sequence of points,
send only the data value without point address for any remaining points in the
sequence, and the Sequence Flag (SQ) will be set to one (1). When SQ = 1, the
Client assumes that all points after the first point use information object
addresses in a contiguous order (using the first point as the reference starting
address).

Note: Refer to the client device specification to verify if this feature is supported before you
consider using it.