2.1.9 [M_ME_NB_1 104]

This section defines the monitored measured value, scaled database for the
server device emulated. This information is sourced from the database and is
transferred to the remote client unit. To determine the IOA (Information Object
Address) for each object, add the Point # (IOA) to the M_ME_NB Parameter
Offset
parameter value as entered in the [IEC-870-5-104 Database] section.

This section takes the following parameters:

Point

#:

DB

Address:

Group(s):
Default

Deadband:

IV DB Bit

Each point is one, 16-bit word and the DB Address value corresponds to the
word offset in the gateway memory database. For additional information on how
to set these parameters, see the 104S Tutorial and Reference chapters of this
manual.

2.1.10 [M_ME_NC_1 104]

This section defines the monitored short-float point database for the slave device
emulated. This information is sourced from the database and is transferred to the
remote client unit. To determine the IOA (Information Object Address) for each
object, add the Point # (IOA) to the M_ME_NC Parameter Offset parameter value
as entered in the [IEC-870-5-104 Database] section.

This section takes the following parameters:

Point

#

DB

Address

Groups
Default

Deadband

IV DB Bit

Each point is two, 16-bit words and the DB Address value corresponds to the
double-word offset in the gateway memory database. For additional information
on how to set these parameters, see the 104S Tutorial and Reference chapters
of this manual.

For a list of Group Codes, refer to the section on Group Codes (page 36).