IEC-60870-5-104 (104S) Protocol Implementation

104S v2 ♦ ProLinx Gateway

Protocol Manual

(Firmware v2.xx)


ProSoft Technology, Inc.

Page 65 of 157

3.4.2 Command Points Addressing

Command points must be configured in a database area that is updated in the
gateway memory database. You must associate each point to a database
address in the 104S v2 gateway. The interpretation of the DB address parameter
in the configuration tables depends on the point type configured and the type of
addressing associated with that point type.

Data Type

Data Size

Addressing Type

C_SC_NA 1

bit

Bit

C_DC_NA 2

bits

Bit

C_RC_NA 1

byte

Byte

C_BO_NA 2

words

Double-word

C_SE_NA 1

word

Word

C_SE_NB 1

word

Word

C_SE_NC 2

words

Double-word

C_SC_NA and C_DC_NA

The single-point command and dual-point command points use one bit with bit-
addressing. For example, if you configure the following points:

These points would be used as follows:

Inf. Object Address

Module Database Address

100

Bit 0 of word 100

101

Bit 1 of word 100

102

Bit 2 of word 100

March 19, 2010