3.4

Using Control (Command) Points

The following control points are supported by the 104S v2 gateway:

Symbol Description

C_SC_NA Single-Point

Command

C_DC_NA Dual-Point

Command

C_RC_NA Step-Point

Command

C_SE_NA

Measured Normalized Point Command

C_SE_NB

Measured Scaled-Point Command

C_SE_NC

Measured Short Floating-Point Command

Each control point is identified by its Information Object Address. For each
control point, configure the following parameters:

Point #: This is the information object address of the point. It identifies the point
in the network. This address must be unique for each Common ASDU Address in
the network.

DB Address: This is the database location in the 104S v2 gateway associated
with the point.

Monitor Point #-Monitor DB Address- The user might (optionally) configure a
monitor point to be sent by the 104S v2 module gatewayt receives the command
for that specific point.