System or device, Application layer, Transmission mode for application data – ProSoft Technology 5201-DFNT-104S User Manual

Page 128: Common address of asdu, Information object address, Cause of transmission, Length of apdu

Advertising
background image

104S v2 ♦ ProLinx Gateway

Reference

(Firmware v2.xx)

Protocol Manual


Page 128 of 157

ProSoft Technology, Inc.

March 19, 2010

A black check box indicates that the option cannot be selected in this companion
standard.

5.7.1 System or device

System definition

Controlling station definition (Master)

⌧ Controlled station definition (Slave)

5.7.2 Application Layer

Transmission mode for application data

Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4,
is used exclusively in this companion standard.

Common Address of ASDU

(System-specific parameter)

One octet

⌧ Two octets

Information object address

(System-specific parameter)

One octet

Structured

Two octets

Unstructured

⌧ Three octets

Cause of transmission

(System-specific parameter)

One octet

⌧ Two octets (with originator address)

Length of APDU

(System-specific parameter, specify the maximum length of the APDU per
system)

The Maximum length of the APDU is 246 (default). The maximum length may be
reduced by the system.

246 Maximum length of APDU per system

Advertising